Technical specification of DC Vega data center
DC Vega is a commercial data center in Prague 9 - Střížkov with redundant A/B power, N+1 to N+2 cooling, RC3 physical security and Novec 1230 gas suppression. Operations are monitored 24/7/365.
Power
- Architecture
- A/B power – two independent branches
- Distribution
- Each branch has its own switchboard, UPS and batteries
- Backup
- Each branch has its own diesel generator
Cooling
- Parameters
- Up to 25 °C, 40–60% humidity
- Minimum configuration
- N+1
- Typical operation
- N+2 configuration for most of the year
Connectivity
- Aggregation
- Aggregated connectivity according to operational needs
- Dedicated lines
- Dedicated line directly from the operator
- Interconnects
- Cross-connects within the hall, dark fiber to another location
Security
- Structural level
- Data hall walls in RC3 category
- Access control
- Customer check by ID documents + DC supervision
- ACS + CCTV
- ACS + CCTV, record retention
Monitoring
- DC monitoring
- SW MIDS – DC parameters
- Batteries
- Continuous Cellwatch monitoring
- Escalation
- 24/7/365
Fire Protection
- Suppression
- Stable gas extinguishing GHZ, Novec 1230
- Impact on HW
- Electronics-safe, no water in the hall
- Zoning
- Zoning limits impact of intervention
Glossary
- N+1
- At least one spare unit beyond the operational minimum – if one fails, capacity is maintained.
- A/B power
- Two fully independent electrical branches, each with its own switchboard, UPS and diesel generator. A failure on one branch does not affect operations.
- RC3
- Wall resistance class per EN 1627 – protection against forced entry attempts using tools.
- Novec 1230
- A clean fire suppression agent that leaves no residue and is safe for electronics – replacing older halon-based systems.